REACTOR SWITCHING TESTS OF A VACUUM CIRCUIT BREAKER, FARGO SUBSTATION MISSOURI RIVER BASIN PROJECT,

G. W. Cleaveland, Starkenberg,C. U. T.

Open publisher page 0 citations

Abstract

A 13.8-kv vacuum-type circuit breaker at Fargo Substation performed well on reactor switching tests, usually clearing at the first current zero after contact part (for the first contact to clear). Average arcing time for the 3 phases was 0.35 cycles. This new-type breaker shows no tendency to restriking but a slight tendency to current chopping with breaker operating at 84% of continuous current rating. Moderate overvoltage transients were recorded during closing operations. The tests demonstrate a very regular pattern of clearing by the 3 interrupters during point-on-cycle switching. This breaker can be expected to provide reasonably maintenance-free reactor switching service and reasonable life within its range of applicability. Since it has low interrupting capabilities (12,000 amp, symmetrical) its use would be limited normally to locations with fault currents at or below this amount. At stations with higher interrupting current capabilities, the advantages of a vacuum breaker can be used for reactor switching service if it is applied between the reactor and the reactor neutral or by protecting the circuit with fuses of adequate interrupting capabilities. Since these tests do not provide information on interrupter life or frequency of contact adjustment, the breaker should be left in service for further study. (Author)

About this research paper

What this paper is about

A 13.8-kv vacuum-type circuit breaker at Fargo Substation performed well on reactor switching tests, usually clearing at the first current zero after contact part (for the first contact to clear). Average arcing time for the 3 phases was 0.35 cycles. This new-type breaker shows no tendency to restriking but a slight tendency to current chopping with breaker operating at 84% of continuous current rating. Moderate overvoltage transients were recorded during closing operations. The tests demonstrate a very regular pattern of clearing by the 3 interrupters during point-on-cycle switching. This breaker can be expected to provide reasonably maintenance-free reactor switching service and reasonable life within its range of applicability. Since it has low interrupting capabilities (12,000 amp, symmetrical) its use would be limited normally to locations with fault currents at or below this amount. At stations with higher interrupting current capabilities, the advantages of a vacuum breaker can be used for reactor switching service if it is applied between the reactor and the reactor neutral or by protecting the circuit with fuses of adequate interrupting capabilities. Since these tests do not provide information on interrupter life or frequency of contact adjustment, the breaker should be left in service for further study. (Author)

Why it matters

A significance statement is not available in the OpenAlex record.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

A 13.8-kv vacuum-type circuit breaker at Fargo Substation performed well on reactor switching tests, usually clearing at the first current zero after contact part (for the first contact to clear). Average arcing time for the 3 phases was 0.35 cycles. This new-type breaker shows no tendency to restriking but a slight tendency to current chopping with breaker operating at 84% of continuous current rating. Moderate overvoltage transients were recorded during closing operations. The tests demonstrate a very regular pattern of clearing by the 3 interrupters during point-on-cycle switching. This breaker can be expected to provide reasonably maintenance-free reactor switching service and reasonable life within its range of applicability. Since it has low interrupting capabilities (12,000 amp, symmetrical) its use would be limited normally to locations with fault currents at or below this amount. At stations with higher interrupting current capabilities, the advantages of a vacuum breaker can be used for reactor switching service if it is applied between the reactor and the reactor neutral or by protecting the circuit with fuses of adequate interrupting capabilities. Since these tests do not provide information on interrupter life or frequency of contact adjustment, the breaker should be left in service for further study. (Author)

Key concepts: Circuit breaker, Interrupter, Arc-fault circuit interrupter, Transient recovery voltage, Electrical engineering, Overvoltage, Sulfur hexafluoride circuit breaker, Residual-current device