2007IEEJ Transactions on Power and EnergyOpen access

Current Zero Missing Phenomena caused by D.C. Current which Flows from Shunt Reactor at the Ground Fault and its Interruption

Takayuki Kobayashi, Atsushi Eto, Tadashi Koshizuka, S. Nishiwaki, Kietsu Kudo, K. Matsushita, Osamu Hosokawa

Open full text 2 citations

Abstract

At substations where shunt reactors are installed, when a ground fault occurs near the reactor, d.c. current flows from the reactor to the fault point. There are cases where circuit breakers installed near the reactor interrupt only the d.c. current from the reactor with long arcing times. In those cases, attention should be paid to the damage of the contacts.This paper shows the investigation of the d.c. current interrupting performance for the 550kV one-break SF6 gas circuit breaker. In the range of some hundreds amperes, the d.c. arc voltages with long arcing times of the 550kV one-break circuit breaker were measured. The d.c. current waveform and arcing time at the d.c. current interruption by 550kV one-break circuit breaker in the 500kV cable system were calculated. Interrupting test circuit for the d.c. current interruption was constructed in the high power laboratory. From the interrupting test results, it was made clear that the circuit breaker had a good interrupting performance after the d.c. current interruptions.

Open-access reader

About this research paper

What this paper is about

At substations where shunt reactors are installed, when a ground fault occurs near the reactor, d.c. current flows from the reactor to the fault point. There are cases where circuit breakers installed near the reactor interrupt only the d.c. current from the reactor with long arcing times. In those cases, attention should be paid to the damage of the contacts.This paper shows the investigation of the d.c. current interrupting performance for the 550kV one-break SF6 gas circuit breaker. In the range of some hundreds amperes, the d.c. arc voltages with long arcing times of the 550kV one-break circuit breaker were measured. The d.c. current waveform and arcing time at the d.c. current interruption by 550kV one-break circuit breaker in the 500kV cable system were calculated. Interrupting test circuit for the d.c. current interruption was constructed in the high power laboratory. From the interrupting test results, it was made clear that the circuit breaker had a good interrupting performance after the d.c. current interruptions.

Why it matters

OpenAlex reports 2 citations for this work. Citation counts describe recorded attention and do not establish research quality.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

At substations where shunt reactors are installed, when a ground fault occurs near the reactor, d.c. current flows from the reactor to the fault point. There are cases where circuit breakers installed near the reactor interrupt only the d.c. current from the reactor with long arcing times. In those cases, attention should be paid to the damage of the contacts.This paper shows the investigation of the d.c. current interrupting performance for the 550kV one-break SF6 gas circuit breaker. In the range of some hundreds amperes, the d.c. arc voltages with long arcing times of the 550kV one-break circuit breaker were measured. The d.c. current waveform and arcing time at the d.c. current interruption by 550kV one-break circuit breaker in the 500kV cable system were calculated. Interrupting test circuit for the d.c. current interruption was constructed in the high power laboratory. From the interrupting test results, it was made clear that the circuit breaker had a good interrupting performance after the d.c. current interruptions.

Key concepts: Circuit breaker, Arc-fault circuit interrupter, Transient recovery voltage, Sulfur hexafluoride circuit breaker, Electrical engineering, Residual-current device, Current (fluid), Prospective short circuit current