CAUSE ANALYSIS FOR STALL OF AXIAL FANS OPERATING IN PARALLEL
Jiaxin Wang
Abstract
Jiaxin Wang
Abstract
The stall of a forced draft fan and a primary air fan for boiler no.2 in one power plant has been analysed.Through test and inspection,it was found that the main cause leading to stall of the forced draft fan is reversely installed the outlet guide blades,and that leading to stall of the primary air fan is most higher ventilation resistance and most higher outlet temperature of the coal pulveri-zer.After retrofitting,no stall appears again on the said forced draft fan and the primary air fan.
A significance statement is not available in the OpenAlex record.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
The stall of a forced draft fan and a primary air fan for boiler no.2 in one power plant has been analysed.Through test and inspection,it was found that the main cause leading to stall of the forced draft fan is reversely installed the outlet guide blades,and that leading to stall of the primary air fan is most higher ventilation resistance and most higher outlet temperature of the coal pulveri-zer.After retrofitting,no stall appears again on the said forced draft fan and the primary air fan.