Experimental Study of a Novel Indirect Evaporative Cooler
Yu Gang Wang, Jia Ping Liu, Huang Xiang
Abstract
Yu Gang Wang, Jia Ping Liu, Huang Xiang
Abstract
Set up a test-bed, test the pre-cooling section, cooling section, and the units consist of them separately, then analysis the data. Within the experimental range, the best ratio of the secondary air volume and the primary air volume is 1.2 for the pre-cooling section, for the cooling section is 1.69. The outlet air temperature is below its wet bulb temperature for the units, and higher than its dew point temperature.
A significance statement is not available in the OpenAlex record.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
Set up a test-bed, test the pre-cooling section, cooling section, and the units consist of them separately, then analysis the data. Within the experimental range, the best ratio of the secondary air volume and the primary air volume is 1.2 for the pre-cooling section, for the cooling section is 1.69. The outlet air temperature is below its wet bulb temperature for the units, and higher than its dew point temperature.
Key concepts: Evaporative cooler, Dew point, Section (typography), Wet-bulb temperature, Volume (thermodynamics), Meteorology, Materials science, Range (aeronautics)