THEORETICAL ANALYSIS OF LINED -DUCT SOUND ATTENUATION
Chris Bibby, Murray Hodgson
Abstract
Open-access reader
Chris Bibby, Murray Hodgson
Abstract
Open-access reader
This paper investigates theoretically how duct geometry and liner thickness affect the attenuation of fundamental-mode sound propagation in a lined duct.The study was done to satisfy the need for a greater understanding of interior naturalventilation openings and of silencers implemented to improve the acoustical performance ('ventilators'), and to provide engineers and architects with optimal-design guidelines.It assumed ventilators of the simplest formstraight, acousticallylined ducts of rectangular cross-section.An analytical solution is presented for the attenuation of the fundamental mode in such a duct.Duct-liner thickness does not affect high-frequency performance; however, it limits low-frequency performance.A 25-mm liner is likely not thick enough to be effective, but a 100-mm liner may be excessive.Increasing the duct height reduces the attenuation at all frequencies; in order to provide effective attenuation through the 4000-Hz band, the height should not exceed 100 mm.If the cross-sectional aspect ratio of a duct is greater than 10, or the duct is only lined on two opposing surfaces, the attenuation of its fundamental mode is in effect identical to that of a 2D lined duct.Provided that the duct liner and height are such that the silencer is effective at absorbing sound at a given frequency, reducing the aspect ratio towards unity will result in large attenuation gains.
OpenAlex reports 2 citations for this work. Citation counts describe recorded attention and do not establish research quality.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
This paper investigates theoretically how duct geometry and liner thickness affect the attenuation of fundamental-mode sound propagation in a lined duct.The study was done to satisfy the need for a greater understanding of interior naturalventilation openings and of silencers implemented to improve the acoustical performance ('ventilators'), and to provide engineers and architects with optimal-design guidelines.It assumed ventilators of the simplest formstraight, acousticallylined ducts of rectangular cross-section.An analytical solution is presented for the attenuation of the fundamental mode in such a duct.Duct-liner thickness does not affect high-frequency performance; however, it limits low-frequency performance.A 25-mm liner is likely not thick enough to be effective, but a 100-mm liner may be excessive.Increasing the duct height reduces the attenuation at all frequencies; in order to provide effective attenuation through the 4000-Hz band, the height should not exceed 100 mm.If the cross-sectional aspect ratio of a duct is greater than 10, or the duct is only lined on two opposing surfaces, the attenuation of its fundamental mode is in effect identical to that of a 2D lined duct.Provided that the duct liner and height are such that the silencer is effective at absorbing sound at a given frequency, reducing the aspect ratio towards unity will result in large attenuation gains.
Key concepts: Duct (anatomy), Attenuation, Silencer, Acoustic attenuation, Acoustics, Expansion chamber, Materials science, Engineering