Analysis of centrifugal chillers with oil-free magnetic bearings for enhancing building energy performance
F.W. Yu, K.T. Chan, R.K.Y. Sit
Abstract
F.W. Yu, K.T. Chan, R.K.Y. Sit
Abstract
This article examines the actual operating performance of centrifugal chillers with oil-free magnetic bearings (hereafter oil-free chillers) to analyze energy saving potentials for commercial buildings. A chiller system retrofit for a shopping arcade involved replacing three existing constant speed water-cooled centrifugal chillers by three oil-free centrifugal chillers of the same capacity. The coefficient of performance was calculated based on operating data logged at 1-h intervals for over 1 year before and after replacement. Oil-free chillers with variable speed control operated at a higher coefficient of performance under part load conditions, reducing the total electricity consumption of the shopping arcade by 9.6%. If the average technical efficiency in data envelopment analysis was improved to 1 from 0.6 in the existing case, the average system coefficient of performance could increase from 6.2 to 10.3. The improvement involved controlling the temperature of supply chilled water at a lower boundary curve and operating an equal percentage of capacity among chillers. It is economically viable to design an all-variable speed chiller system with oil-free chillers instead of the conventional constant speed system for a reference office building in a subtropical climate.
OpenAlex reports 11 citations for this work. Citation counts describe recorded attention and do not establish research quality.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
This article examines the actual operating performance of centrifugal chillers with oil-free magnetic bearings (hereafter oil-free chillers) to analyze energy saving potentials for commercial buildings. A chiller system retrofit for a shopping arcade involved replacing three existing constant speed water-cooled centrifugal chillers by three oil-free centrifugal chillers of the same capacity. The coefficient of performance was calculated based on operating data logged at 1-h intervals for over 1 year before and after replacement. Oil-free chillers with variable speed control operated at a higher coefficient of performance under part load conditions, reducing the total electricity consumption of the shopping arcade by 9.6%. If the average technical efficiency in data envelopment analysis was improved to 1 from 0.6 in the existing case, the average system coefficient of performance could increase from 6.2 to 10.3. The improvement involved controlling the temperature of supply chilled water at a lower boundary curve and operating an equal percentage of capacity among chillers. It is economically viable to design an all-variable speed chiller system with oil-free chillers instead of the conventional constant speed system for a reference office building in a subtropical climate.
Key concepts: Chiller, Chiller boiler system, Coefficient of performance, Electricity, Engineering, Chilled water, Automotive engineering, Environmental science