Analysis and optimization of quality of inner cooling water in 362.5MW generators
Zhong Lian
Abstract
Zhong Lian
Abstract
Since 2×362.5MW units imported from UK in Huaneng Yueyang Power Plant put into operation,PH value of generator inner cooling water has been extra low and inner wall of stator bar has been badly eroded and blocked.Inner generator cooling water is treated by ion exchange micro-basification and water turns to micro-basification,effectively controlling erode of copper coil.Water quality then exceeds GB standard and scheduled object is achieved.
A significance statement is not available in the OpenAlex record.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
Since 2×362.5MW units imported from UK in Huaneng Yueyang Power Plant put into operation,PH value of generator inner cooling water has been extra low and inner wall of stator bar has been badly eroded and blocked.Inner generator cooling water is treated by ion exchange micro-basification and water turns to micro-basification,effectively controlling erode of copper coil.Water quality then exceeds GB standard and scheduled object is achieved.
Key concepts: Generator (circuit theory), Stator, Water cooling, Power station, Electromagnetic coil, Environmental engineering, Heat exchanger, Waste management