The 6 kV working busbar 2MCA of Unit 2 in Shenzhen Mawan General Power Plant experienced virtual earthing while being put into operation and switching off the LV working transformer 42T A respectively. It is concluded upon analysis that the virtual earthing was caused by the power frequency resonance between the inductance coil of the voltage transformer and the busbar-to-ground capacitance,which led to neutral displacement and the unsymmetrical three phase-to-ground voltages,and in turn gave rise to zero-sequence voltage Finally, suggestions for eliminating the resonance are put forth in this paper.
A significance statement is not available in the OpenAlex record.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
The 6 kV working busbar 2MCA of Unit 2 in Shenzhen Mawan General Power Plant experienced virtual earthing while being put into operation and switching off the LV working transformer 42T A respectively. It is concluded upon analysis that the virtual earthing was caused by the power frequency resonance between the inductance coil of the voltage transformer and the busbar-to-ground capacitance,which led to neutral displacement and the unsymmetrical three phase-to-ground voltages,and in turn gave rise to zero-sequence voltage Finally, suggestions for eliminating the resonance are put forth in this paper.
Key concepts: Busbar, Ground, Electrical engineering, Engineering, Transformer, Inductance, Voltage, Electromagnetic coil