2004Dianli zidonghua shebeiRequires access

Transformer saturation criterion for line differential protection

Qiang Wang

Open publisher page 3 citations

Abstract

CT(Current Transformer) saturation at external fault of short line and other special con-ditions will cause misoperation of line current differential protection for EHV / HV transmission line. Some preventive measures such as increasing setting threshold and enhancing restraint factor will reduce the protection sensitivity and delay the protective action. A CT saturation detection method is introduced,which combines short data window with distinguishing wave distortion. It ensures both sensitivity for internal faults and reliability for external faults,which is successfully applied in digital fiber current differential protection with 32 - bit DSP.

About this research paper

What this paper is about

CT(Current Transformer) saturation at external fault of short line and other special con-ditions will cause misoperation of line current differential protection for EHV / HV transmission line. Some preventive measures such as increasing setting threshold and enhancing restraint factor will reduce the protection sensitivity and delay the protective action. A CT saturation detection method is introduced,which combines short data window with distinguishing wave distortion. It ensures both sensitivity for internal faults and reliability for external faults,which is successfully applied in digital fiber current differential protection with 32 - bit DSP.

Why it matters

OpenAlex reports 3 citations for this work. Citation counts describe recorded attention and do not establish research quality.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

CT(Current Transformer) saturation at external fault of short line and other special con-ditions will cause misoperation of line current differential protection for EHV / HV transmission line. Some preventive measures such as increasing setting threshold and enhancing restraint factor will reduce the protection sensitivity and delay the protective action. A CT saturation detection method is introduced,which combines short data window with distinguishing wave distortion. It ensures both sensitivity for internal faults and reliability for external faults,which is successfully applied in digital fiber current differential protection with 32 - bit DSP.

Key concepts: Differential protection, Current transformer, Transmission line, Transformer, Electronic engineering, Fault detection and isolation, Engineering, Control theory (sociology)