Fault Analysis of A 110 kV Substation Total Power Loss Caused by Dead Zone Fault of Main Transformer

Zhou Cha

Open publisher page 0 citations

Abstract

The paper describes the relay operation,reason and improvement measures of a 110 kV substation power failure caused by the dead zone fault of a main transformer.By analyzing the protective action report and recorded wave,the high backup protection didn't act,because the compound blocking condition was not open.Then the fault caused distanceⅢ segment action of the lateral line,the protective action of the 110 kV spare power automatic switching device,and the differential action of main transformer,which eventually led to the substation power failure.

About this research paper

What this paper is about

The paper describes the relay operation,reason and improvement measures of a 110 kV substation power failure caused by the dead zone fault of a main transformer.By analyzing the protective action report and recorded wave,the high backup protection didn't act,because the compound blocking condition was not open.Then the fault caused distanceⅢ segment action of the lateral line,the protective action of the 110 kV spare power automatic switching device,and the differential action of main transformer,which eventually led to the substation power failure.

Why it matters

A significance statement is not available in the OpenAlex record.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

The paper describes the relay operation,reason and improvement measures of a 110 kV substation power failure caused by the dead zone fault of a main transformer.By analyzing the protective action report and recorded wave,the high backup protection didn't act,because the compound blocking condition was not open.Then the fault caused distanceⅢ segment action of the lateral line,the protective action of the 110 kV spare power automatic switching device,and the differential action of main transformer,which eventually led to the substation power failure.

Key concepts: Backup, Transformer, Relay, Electrical engineering, Spare part, Engineering, Fault (geology), Ground

Related papers

Back to paper searchBrowse research topicsOriginal source
Fault Analysis of A 110 kV Substation Total Power Loss Caused by Dead Zone Fault of Main Transformer — Research Paper | ScholarLens