2008Unpublished venueRequires access

Ultra-high frequency spectral characteristics of partial discharge in insulation oil

Sun-Geun Goo, Hyeongjun Ju, Kijun Park, Ki-Seon Han, Jinyul Yoon

Open publisher page 6 citations

Abstract

We have designed and manufactured four types of typical defects found in power transformers to simulate partial discharge(PD) in oil insulated power transformers. Stable PD signals were generated by applying AC voltages on to the PD cells. We measured spectral response of PD signals from these defects using our Ultra-high frequency(UHF) PD measuring system and apparent discharge using IEC60270 PD detector simultaneously. Partial discharges from the defects in oil generated well detectable UHF signal up to about 2 GHz. UHF PD patterns were recorded and analyzed for each defect types. The phase resolved partial discharge(PRPD) patterns of defect obtained from UHF range were different from each other. The patterns of UHF PD signals were also different from those obtained from that of conventional method. Type of defect could be identified by obtaining PRPD patterns.

About this research paper

What this paper is about

We have designed and manufactured four types of typical defects found in power transformers to simulate partial discharge(PD) in oil insulated power transformers. Stable PD signals were generated by applying AC voltages on to the PD cells. We measured spectral response of PD signals from these defects using our Ultra-high frequency(UHF) PD measuring system and apparent discharge using IEC60270 PD detector simultaneously. Partial discharges from the defects in oil generated well detectable UHF signal up to about 2 GHz. UHF PD patterns were recorded and analyzed for each defect types. The phase resolved partial discharge(PRPD) patterns of defect obtained from UHF range were different from each other. The patterns of UHF PD signals were also different from those obtained from that of conventional method. Type of defect could be identified by obtaining PRPD patterns.

Why it matters

OpenAlex reports 6 citations for this work. Citation counts describe recorded attention and do not establish research quality.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

We have designed and manufactured four types of typical defects found in power transformers to simulate partial discharge(PD) in oil insulated power transformers. Stable PD signals were generated by applying AC voltages on to the PD cells. We measured spectral response of PD signals from these defects using our Ultra-high frequency(UHF) PD measuring system and apparent discharge using IEC60270 PD detector simultaneously. Partial discharges from the defects in oil generated well detectable UHF signal up to about 2 GHz. UHF PD patterns were recorded and analyzed for each defect types. The phase resolved partial discharge(PRPD) patterns of defect obtained from UHF range were different from each other. The patterns of UHF PD signals were also different from those obtained from that of conventional method. Type of defect could be identified by obtaining PRPD patterns.

Key concepts: Partial discharge, Ultra high frequency, Materials science, Transformer, Insulation system, Voltage, Detector, High voltage

Related papers

Back to paper searchBrowse research topicsOriginal source
Ultra-high frequency spectral characteristics of partial discharge in insulation oil — Research Paper | ScholarLens