1991IEEE Power Engineering ReviewRequires access

A Stand-alone Digital Protective Relay for Power Transformers

I. Hermanto, Y.V.V.S. Murty, M.A. Rahman

Open publisher page 19 citations

Abstract

The complete design of a stand-alone prototype digital protective relay for three-phase power transformers is described. The major emphasis is on the detailed description of the hardware and software of the prototype relay. The protection functions implemented include: a percentage differential protection with a second-harmonic restraint for magnetizing inrush and a fifth-harmonic restraint for overexcitation conditions, and a separate protection for high-impedance primary and secondary ground faults. The relay design is tested with the Fourier algorithm, and any other relay algorithm can be used by replacing only one subroutine. The relay hardware consists of a data acquisition board and a digital processing board which is based on the TMS320E15 processor. Sample real-time test cases are discussed. The results show that the relay never misoperated and correctly identified all the faults. >

About this research paper

What this paper is about

The complete design of a stand-alone prototype digital protective relay for three-phase power transformers is described. The major emphasis is on the detailed description of the hardware and software of the prototype relay. The protection functions implemented include: a percentage differential protection with a second-harmonic restraint for magnetizing inrush and a fifth-harmonic restraint for overexcitation conditions, and a separate protection for high-impedance primary and secondary ground faults. The relay design is tested with the Fourier algorithm, and any other relay algorithm can be used by replacing only one subroutine. The relay hardware consists of a data acquisition board and a digital processing board which is based on the TMS320E15 processor. Sample real-time test cases are discussed. The results show that the relay never misoperated and correctly identified all the faults. >

Why it matters

OpenAlex reports 19 citations for this work. Citation counts describe recorded attention and do not establish research quality.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

The complete design of a stand-alone prototype digital protective relay for three-phase power transformers is described. The major emphasis is on the detailed description of the hardware and software of the prototype relay. The protection functions implemented include: a percentage differential protection with a second-harmonic restraint for magnetizing inrush and a fifth-harmonic restraint for overexcitation conditions, and a separate protection for high-impedance primary and secondary ground faults. The relay design is tested with the Fourier algorithm, and any other relay algorithm can be used by replacing only one subroutine. The relay hardware consists of a data acquisition board and a digital processing board which is based on the TMS320E15 processor. Sample real-time test cases are discussed. The results show that the relay never misoperated and correctly identified all the faults. >

Key concepts: Digital protective relay, Relay, Inrush current, Protective relay, Differential protection, Solid-state relay, Transformer, Computer science

Related papers

Back to paper searchBrowse research topicsOriginal source
A Stand-alone Digital Protective Relay for Power Transformers — Research Paper | ScholarLens