Cone calorimeter and room corner fire testing of balsa wood core/phenolic composite skin sandwich panels
Alexander B. Morgan, Elias A. Toubia
Abstract
Alexander B. Morgan, Elias A. Toubia
Abstract
Polymer composite sandwich core panels are of interest for lightweight construction and portable shelter use. In this article, material selection and construction design were considered for an application which required a high level of fire safety performance. Phenolic + fiberglass skin composites with balsa wood core sandwich panels were constructed and first screened for fire performance with the cone calorimeter (ASTM E1354) at different heat fluxes. From these data, fire testing in the room corner test (ISO 9705) was conducted. The results indicated that these composites could only pass the room corner test if an aluminum skin was used to provide some additional fire protection to the underlying composite. Furthermore, it was found that cone calorimeter testing at very high heat flux (100 kW/m 2 ) was not always indicative of fire performance in the room corner test. How the aluminum skin was mechanically attached to the panel as well as underlying composite construction played an important role in the full-scale fire test results.
OpenAlex reports 10 citations for this work. Citation counts describe recorded attention and do not establish research quality.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
Polymer composite sandwich core panels are of interest for lightweight construction and portable shelter use. In this article, material selection and construction design were considered for an application which required a high level of fire safety performance. Phenolic + fiberglass skin composites with balsa wood core sandwich panels were constructed and first screened for fire performance with the cone calorimeter (ASTM E1354) at different heat fluxes. From these data, fire testing in the room corner test (ISO 9705) was conducted. The results indicated that these composites could only pass the room corner test if an aluminum skin was used to provide some additional fire protection to the underlying composite. Furthermore, it was found that cone calorimeter testing at very high heat flux (100 kW/m 2 ) was not always indicative of fire performance in the room corner test. How the aluminum skin was mechanically attached to the panel as well as underlying composite construction played an important role in the full-scale fire test results.
Key concepts: Cone calorimeter, Sandwich-structured composite, Fire performance, Fire test, Composite number, Composite material, Calorimeter (particle physics), Core (optical fiber)