Performance of Variable-air-volume Air-conditioning System under Reduced Static Pressure Control in an Occupied Office
Ryan L. Y. Lee, T.T. Chow
Abstract
Ryan L. Y. Lee, T.T. Chow
Abstract
Traditional control of variable air volume (VAV) air conditioning system in office building keeps static pressure in main air duct at constant pressure. This provides excessive static pressure during partial load, resulting in energy wastage. In this study, retrofit control algorithm is adopted to minimize static pressure in main air ducts by varying the static pressure set point. Though static pressure optimization studies were performed in the past, the control methods were implemented to the VAV system either in unoccupied office or by simulation. This paper describes a year round field study that applied a reduced static pressure algorithm to an occupied office floor. Thermal comfort and indoor air quality were evaluated. The results revealed that 8–9% annual energy saving is achievable without sacrificing thermal comfort and indoor air quality.
OpenAlex reports 6 citations for this work. Citation counts describe recorded attention and do not establish research quality.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
Traditional control of variable air volume (VAV) air conditioning system in office building keeps static pressure in main air duct at constant pressure. This provides excessive static pressure during partial load, resulting in energy wastage. In this study, retrofit control algorithm is adopted to minimize static pressure in main air ducts by varying the static pressure set point. Though static pressure optimization studies were performed in the past, the control methods were implemented to the VAV system either in unoccupied office or by simulation. This paper describes a year round field study that applied a reduced static pressure algorithm to an occupied office floor. Thermal comfort and indoor air quality were evaluated. The results revealed that 8–9% annual energy saving is achievable without sacrificing thermal comfort and indoor air quality.
Key concepts: Variable air volume, Static pressure, Air conditioning, Duct (anatomy), Thermal comfort, Room air distribution, Pressure control, Volume (thermodynamics)