A New Algorithm to Avoid Maloperation of Transformer Differential Protection in Substations With an Inner Bridge Connection
Tao Zheng, Jiebin Gu, Shan Huang, Fang Guo, Vladimir V. Terzija
Abstract
Tao Zheng, Jiebin Gu, Shan Huang, Fang Guo, Vladimir V. Terzija
Abstract
In substations with an inner bridge connection, the two main transformers are generally connected in parallel. The differential protection of the transformer, under normal operating conditions, may maloperate when the other transformer is switching on through the bridge breaker after scheduled maintenance. This paper analyzes the factors that may lead to the maloperation of transformer differential protection and concludes that local transient saturation of the current transformer (CT) caused by the decaying dc component in the magnetizing inrush is the main cause of the maloperation of the transformer differential protection. By detecting the time difference between the instant of sudden changes occurring in the transformer wye-side current and the instant of the differential current increasing, a new algorithm based on the time differential method is proposed in this paper, which can prevent the maloperation of transformer differential protection in substations with an inner bridge connection. On the basis of detailed analysis and simulation work, the new algorithm is verified to be applicable under the conditions of sympathetic inrush and CT saturation.
OpenAlex reports 37 citations for this work. Citation counts describe recorded attention and do not establish research quality.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
In substations with an inner bridge connection, the two main transformers are generally connected in parallel. The differential protection of the transformer, under normal operating conditions, may maloperate when the other transformer is switching on through the bridge breaker after scheduled maintenance. This paper analyzes the factors that may lead to the maloperation of transformer differential protection and concludes that local transient saturation of the current transformer (CT) caused by the decaying dc component in the magnetizing inrush is the main cause of the maloperation of the transformer differential protection. By detecting the time difference between the instant of sudden changes occurring in the transformer wye-side current and the instant of the differential current increasing, a new algorithm based on the time differential method is proposed in this paper, which can prevent the maloperation of transformer differential protection in substations with an inner bridge connection. On the basis of detailed analysis and simulation work, the new algorithm is verified to be applicable under the conditions of sympathetic inrush and CT saturation.
Key concepts: Inrush current, Differential protection, Current transformer, Transformer, Engineering, Circuit breaker, Linear variable differential transformer, Control theory (sociology)