2003•IEE Proceedings - Generation Transmission and DistributionRequires access

Discrete-Fourier-transform-based technique for removal of decaying DC offset from phasor estimates

Tarlochan Singh Sidhu, Xindan Zhang, Fadhel Abbas Albasri, Manoj Sachdev

Open publisher page 108 citations

Abstract

A technique to suppress the negative effect of a decaying DC offset on phasor estimates using a digital Fourier transform algorithm is presented. The proposed technique is based on evaluation of the decaying DC component in the signal. The technique is suitable for all prevailing systems and fault conditions. The performance of the technique is evaluated in both the time and frequency domains. Simulation results showing the effectiveness of this new technique are presented. The proposed technique is further evaluated when it is used in a distance relay design.

About this research paper

What this paper is about

A technique to suppress the negative effect of a decaying DC offset on phasor estimates using a digital Fourier transform algorithm is presented. The proposed technique is based on evaluation of the decaying DC component in the signal. The technique is suitable for all prevailing systems and fault conditions. The performance of the technique is evaluated in both the time and frequency domains. Simulation results showing the effectiveness of this new technique are presented. The proposed technique is further evaluated when it is used in a distance relay design.

Why it matters

OpenAlex reports 108 citations for this work. Citation counts describe recorded attention and do not establish research quality.

Key contribution

A contribution statement is not available in the OpenAlex record.

Method / approach

Method details are not available in the OpenAlex metadata.

Main findings

Findings are not separately available in the OpenAlex metadata.

Limitations

Limitations are not available in the OpenAlex metadata.

Applications

Application details are not available in the OpenAlex metadata.

Available abstract

A technique to suppress the negative effect of a decaying DC offset on phasor estimates using a digital Fourier transform algorithm is presented. The proposed technique is based on evaluation of the decaying DC component in the signal. The technique is suitable for all prevailing systems and fault conditions. The performance of the technique is evaluated in both the time and frequency domains. Simulation results showing the effectiveness of this new technique are presented. The proposed technique is further evaluated when it is used in a distance relay design.

Key concepts: Phasor, DC bias, Offset (computer science), Fourier transform, Algorithm, Electronic engineering, Relay, Fast Fourier transform

Related papers

Back to paper searchBrowse research topicsOriginal source
Discrete-Fourier-transform-based technique for removal of decaying DC offset from phasor estimates — Research Paper | ScholarLens