Ultrahigh Capacity Field Tests on 230-Kv Air-Blast Circuit Breaker at Grand Coulee Power Plant [includes discussion]
A. C. Conger, C. L. Killgore, William Wanger
Abstract
A. C. Conger, C. L. Killgore, William Wanger
Abstract
In March 1951 ultrahigh capacity field tests were made at Grand Coulee Power Plant on a 230-kv air-blast circuit breaker to further the development of high-voltage circuit breakers incorporating high-speed operation. Development from field tests in recent years has produced 230-kv 10,000,000-kva circuit breakers with the interruption taking place within oil. However, this is the first air-blast circuit breaker to be introduced to the American power industry in this voltage class and interrupting capacity. The tests proved that the air-blast circuit breaker is capable of interrupting the current of overhead lines without any restrikes and, therefore, without raising the voltage above the value on the line before the interruption. The circuit breaker interrupted well over its rated capacity of 6,000,000-kva symmetrical and 9,000,000-kva asymmetrical. The maximum interrupted power being 7,850,000-kva symmetrical and 10,500,000-kva asymmetrical, this was higher than any previous tests. The interrupting time was always well below 3 cycles. The absolute maximum was 2-72 cycles and the average about 2.4 cycles. The circuit breaker also interrupted these high values in high-speed reclosing operations with reclosing times of 13 to 14 cycles. The contacts were not changed or even inspected during the whole test series. After nine interruptions with an average power of substantially more than the rated capacity, contact erosion was extremely slight so that the same contacts could have withstood at least the same tests again. The tests have shown that the air-blast circuit breaker is capable of solving any problems arising in modern high-capacity networks.
OpenAlex reports 2 citations for this work. Citation counts describe recorded attention and do not establish research quality.
A contribution statement is not available in the OpenAlex record.
Method details are not available in the OpenAlex metadata.
Findings are not separately available in the OpenAlex metadata.
Limitations are not available in the OpenAlex metadata.
Application details are not available in the OpenAlex metadata.
In March 1951 ultrahigh capacity field tests were made at Grand Coulee Power Plant on a 230-kv air-blast circuit breaker to further the development of high-voltage circuit breakers incorporating high-speed operation. Development from field tests in recent years has produced 230-kv 10,000,000-kva circuit breakers with the interruption taking place within oil. However, this is the first air-blast circuit breaker to be introduced to the American power industry in this voltage class and interrupting capacity. The tests proved that the air-blast circuit breaker is capable of interrupting the current of overhead lines without any restrikes and, therefore, without raising the voltage above the value on the line before the interruption. The circuit breaker interrupted well over its rated capacity of 6,000,000-kva symmetrical and 9,000,000-kva asymmetrical. The maximum interrupted power being 7,850,000-kva symmetrical and 10,500,000-kva asymmetrical, this was higher than any previous tests. The interrupting time was always well below 3 cycles. The absolute maximum was 2-72 cycles and the average about 2.4 cycles. The circuit breaker also interrupted these high values in high-speed reclosing operations with reclosing times of 13 to 14 cycles. The contacts were not changed or even inspected during the whole test series. After nine interruptions with an average power of substantially more than the rated capacity, contact erosion was extremely slight so that the same contacts could have withstood at least the same tests again. The tests have shown that the air-blast circuit breaker is capable of solving any problems arising in modern high-capacity networks.
Key concepts: Circuit breaker, Sulfur hexafluoride circuit breaker, Electrical engineering, Engineering, Arc-fault circuit interrupter, Transient recovery voltage, High voltage, Voltage